Search ILC

Products

The LightLEEDer Emergency UL 924 bypass relay control panel will force relay\'s ON during a normal power outage. This panel has all the same features and functions as a standard LightLEEDer lighting controller, allowing normal control of relays with emergency bypass during a normal power failure event. Relays can be all EM or a combination of normal and EM. Each output has a jumper for selecting Force On, Force Off or No change, this allows for emergency on, load shedding off, or no control selection for each relay. Optional Phase monitoring module and high voltage dividers can be added as required. This LightLEEDer Emergency lighting panel is easy to install, no external devices or complicated wiring configurations needed, reducing material and installation costs.

  • UL 924 emergency lighting bypass
  • Used with UL 1008 transfer switch
  • EM and normal power relays in the same panel
  • Utilize standard R40-1, -2, -3 pole relays
  • Standard LightLEEDer processor and operation
  • Optional 3-Phase monitoring module
  • Made in the USA
Features

General Information:

  • UL 924 bypass relay operation of R40 relays
  • Selectable Force On, Force Off, or No Change
  • Standard Relays supported: R40-1, -2, -3 pole
  • Normal & EM relays in same enclosure
  • High Voltage Dividers for separation
  • 3-Phase optional monitoring module (LL-PMM)
  • Remote test switch option
  • Factory or field configured
  • LightLEEDer standard panel operations supported
  • Network compatible with other LightLEEDer panels or standalone operation
  • Made in the USA
Physical

Specifications

Relays:

  • Superior breaker style design
  • Switch type override control
  • Lockout feature disables control from panel
  • 40 Amps @ 120, 277 and 347 VAC
  • 1-, 2-, or 3-pole configurations

Safeguards:

  • Power surge and spike suppression up to 123 volts on the 24VAC power input
  • Data Line surge and spike suppression up to 8Kv and 15Kv through air
  • Memory retention for firmware and programming up to 200 years and electrostatic discharge to 4Kv
  • Real-Time-Clock time retention 45 days or greater without power
  • Internal memory backup and restore

Physical:

  • Relay bypass output module (RBOM)
  • Optional phase monitoring module (PMM)
  • Double-sided construction for mounting directly to breaker box or stand alone
  • Pre-drilled mounting holes for easy installation
  • Provided with a removable hinged locking door mount door, or optional flush mount door. 4 size enclosure provided with a screw cover.
  • High voltage barriers separate normal, emergency, and class 2 wiring

Electrical:

  • 120 or 277 VAC @ 1 Amp, 347 VAC optional

Operating Environment:

  • Location: Interior space
  • Operating Temp.: 0º to 50º C
  • Humidity: 10% - 90% Non-condensing
  • Atmosphere: Non-explosive/corrosive
  • Vibration: Stationary

Certifications and Approvals:

  • UL CUL 924, 916
  • FCC Part 15, 68
  • Title 24
  • ASHRAE compliant
Accessories