The next generation ILC Apprentice II programmable lighting control panel is redesigned with the best in mind. Network up to 48 control points and up to 32 LightSyncTM devices via RJ-45 ports, connect to your PC via a on-board USB 2.0 port and control via Apprentice II Pro software these are just a few of the updates built into the ILC Apprentice II. Add-on cards are easy to install and add capabilities like DMX control, N2, Modbus, BACnet, LonWorks, TCP/IP, Modem interface, and DTMF telephone switching. The ILC Apprentice II lighting control panel retains the same friendly interface, solid reliability, the flexibility to easily comply with energy codes and ships complete.
  • 365-day programmable Lighting Control Panel
  • Removable hinged locking door standard
  • ILC LightSync switch and accessory ready
  • Network up to 48 control points
  • Panel sizes to accomodate 4, 8, and 16 relay outputs
  • Available with 4 to 48 hardwired inputs
  • 48 programmable relay groups, presets, timers
  • Uses ILC’s new cost-effective Softcross relay or APII 2-pole relay
  • All ON/All OFF push buttons for relay override
  • Daylight Savings Time adjustment and Astro Clock standard
  • Optional Add-on Modules
  • UL Listed FCC approval for commercial use
  • Title 24 certified, ASHRAE 90.1 compliant

 

Features

Programming Options

  • Integral keypad with 4-line LCD display
  • Apprentice II Pro software

Comprehensive User Guide

  • The ILC Apprentice II has a complete User Guide which contains the required information for proper installation and programming

Relay Groups

  • Relays may be assigned to any of 48 available groups or presets
  • Relay groups may be assigned to multiple Timers, Switch Inputs, and other panel functions simplifying programming

Relay Presets

  • Relays may be programmed to any of 48 presets available
  • Presets may be controlled by Switch Inputs and Timers

Open/Close Times

  • Lighting Control Schedules may adjust based on business (retail) Open/Close hours
  • Seven standard Open/Close times and 365 custom daily Open/Close times available
  • Scheduled event may be programmed to occur before, after or at Open/Close times

Relay Functions

  • Each relay may be programmed for ON only, OFF only or ON/OFF control
  • HID multilevel control (specialized output control for multilevel HID ballasts including warm-up sequence)

Switch Types

  • The ILC Apprentice II may be programmed to accept virtually any type of switch input, momentary or maintained
  • Easy direct connection to motion and photo sensing devices via dry contact input
  • Override inputs can Force ON, Force OFF or Hold Status any relay or group of relays
  • Input disable based on time of day

Switch Input to Relay Output Mapping

  • All switch to relay settings are completely soft, requiring no field rewiring when changes are required
  • Any switch can control any combination of 1 to 48 relays

Automatic Power-Up Settings

  • Relays may be programmed to automatically return ON or OFF after a power outage

After Hours Sweeps

  • Individual relay or groups of relays may be programmed to be swept OFF during non-operational hours

Daylight Saving Time Adjustment

  • Automatic adjustment for daylight saving changes (may be enabled or disabled from keypad or software)

Astronomical Clock

  • Automatic calculation of Sunrise and Sunset based on date and geographic position
  • Scheduled events may be programmed to occur before, after or on an astro event

Blink Alert

  • Prior to a scheduled OFF event, lighting loads programmed for a Blink Alert will be momentarily turned OFF then back ON to alert occupants. To avoid the pending OFF sweep, the user simply turns their local switch ON again during the adjustable period (default is 5 min.) prior to the OFF sweep.

Add-On Modules

  • Easy to install add-on modules for applications requiring DMX512, Modbus, N2, BACnet, LonWorks, TCP/IP, Modem serial communications and DTMF telephone switching.

Options

  • Additional switch input board(s).
  • Add-on Modules: easy to install modules for applications requiring DMX512, Modbus, N2, BACnet, LonWorks, TCP/IP, Modem serial communications and DTMF telephone switching.
  • Flush mount trim ring.

 

Specifications

Physical

  • Apprentice lighting controllers are provided with pre-drilled mounting holes for easy mounting to unistrut framing or directly to wall
  • All panels provided with a removable hinged locking door standard
  • UL, NEMA-1 enclosure

Electrical

  • 120 or 277 VAC power supply ready

ILC SoftCross Relays

  • 20 amp ballast, 120 and 277 VAC
  • 20 amp resistive load, 120 and 277 VAC
  • Available in Normally Open (NO) or Normally Closed (NC) configuration

ILC 2-Pole Relays

  • 20 amp ballast
  • 20 amp resistive load
  • 20 amp General
  • Up to 277 VAC/pole controlling 208/240/480 VAC circuits
  • Normally Open (NO) contacts

Operating Environment

  • Location Interior space
  • Operating 0° to 40° C (32° to 90° F) Temperature
  • Relative 10% to 90% Non-condensing Humidity

Certifications

  • UL, CUL
  • FCC approval for commercial use
  • California Title 24

Capacities

  • 4, 8 or 16 ILC SoftCrossTM relays ( SR-1) or APII 2-Pole (2PR) relays

Options

  • Additional switch input board(s)
  • Add-on Modules: easy to install modules for applications requiring DMX512, Modbus, N2, BACnet, LonWorks, TCP/IP, Modem serial communications and DTMF telephone switching.

Configuration

  • Soft configuration with greater than 50 year EEPROM memory retention in absence of power
  • Minimum 45 day clock retention

 

Related Downloadable Documents

The following are the related PDF documents used with this product.


 

Apprentice II Programmable Lighting Controller

Apprentice II Softcross Relay Cut Sheet

Apprentice II 2 Pole Relay Cut Sheet

Apprentice II TCP/IP Module Cut Sheet

 

Apprentice II Input and Relay Board Installation

Apprentice II BACnet and LonWorks Module Installation

Apprentice II TCP/IP Module Installation

Apprentice II TCP/IP Module Configuration

Apprentice II Add-On Module Installation

Apprentice II Trim Ring Installation

Apprentice II Panel Wiring Installation

 

Apprentice II Complete Network Relay Panel Schedule

Apprentice II 4 Relay Panel Schedule

Apprentice II 8 Relay Panel Schedule

Apprentice II 16 Relay Panel Schedule

Transformer 120/277 Primary 24VAC w/ct Details

 

BacNet MSTP Point Map

BacNet IP Point Map

LonWorks Point Map

 

LightMaster Relay Timer Types

LightMaster Switch Input Types


CAT 5 RJ45 Connector Installation

CAT 5 Cable Installation Guideline

Network Cable Run Distance Detail

LightSync Cumulative Power Worksheet


Latitude Longitude for Major Cities

NEC Bulletin


Apprentice II Sales Brochure

Apprentice II Catalog

 

Apprentice II Submittal Files


 

Related Software

The following are the most commonly related softwares used with this product.


ILC Apprentice II Setup Software