LightLEEDer Reliant40 Relays
              Models: R40-1, R40-2, R40-3
            
            
          
                  The Reliant40 relay is designed for durability, flexibility, and ease of use. This relay is a superior relay that employs 4 latching nickel-silver contacts. The relay is available in 1, 2, or 3 pole configurations for controlling 120 VAC to 480 VAC loads. It is UL and C-UL listed and is rated for 120 VAC to 347 VAC per pole with a current rating of up to 40 Amps. This relay carries a high fault SCCR rating of 18,000 Amps @ 347 VAC. It also features a manual toggle switch for ON/OFF activation and a Lock-ON/OFF switch to disable control from the panel electronics. Installation is easy with 1 screw and 1 push-on ribbon connector.
Cutsheets
Installation Guides
Specifications
          Physical:
- .99” Wide x 2.0” High x 4.75” Long (1 pole)
 - Accepts 8-12 AWG stranded Cu wire or 10-12 AWG Solid Cu wire
 - Easy installation into any panel
 - Removable ribbon connector interface
 - Clearly marked connection designations
 
Low Voltage Control:
- 18 to 24 VDC
 - Momentary duty rating
 - 50 milliseconds minimum activation time
 - 50 to 55 Ω coil resistance
 - 100mA @ 5 VDC status & disable contacts
 
Electrical:
- 120, 277 or 347 VAC per pole (controls 208/240/480 loads)
 - 40 Amps HID and ballast loads
 - 40 Amp resistive loads
 - 16 Amp electronic ballast loads (UL's limit)
 - 1.5 Hp @120VAC motor loads
 - 18,000 Symmetrical Amp SCCR @347 VAC
 - Plug-load compatible
 
Operating Environment:
- Location: Interior Space
 - Operating Temp.: 0° to 60° C
 - Humidity: 10% to 90% Non-condensing
 - Atmosphere: Non-explosive/corrosive
 - Vibration: Stationary
 
Certifications:
- UL and CUL Listed
 - FCC
 
Resources
            
          Features
          - Made in the USA
 - UL and CUL listed
 - Suitable for controlling all lighting loads
 - Electronic ballast high current inrush load rating
 - Relay contacts consist of 4 nickel-silver contacts designed for high currents
 - Latching relay holds position without the presence of power, saving energy
 - Plug-load compatible
 - Relay configurations available in 1-, 2-, or 3-pole ganged assemblies
 - Manual lever override switch with highly visible indicator
 - Lock-ON/Lock- OFF feature disables On or OFF control from the electronics
 - Terminals consist of 2 line and 2 load connections
 - Screw-actuated wire clamps for use with 10-12 AWG solid or 8-12 AWG stranded copper wire
 - Easily mounted - as easy as interfacing a tab and securing with a screw
 - Operates in any position
 - Wire strip guide located on the side of the relay