OAWC-DT OAWC-DT

Wall Mount Occupancy Sensor, Dual Tech, Low Voltage

Model: OAWC-DT-120W-R, OAWC-DT-120W

The OAWC-DT combines Ultrasonic (US) and Passive Infrared (PIR) sensor technologies to monitor a room for occupancy to deliver maximum energy savings and ensure the greatest  sensitivity and coverage for tough application without the threat of false triggers. PIR is used to turn the lights ON and then either or both technologies are used to keep the lights ON.   The sensor includes MicroSet self-adaptive technology that continuously self-adjusts sensitivity and time delay in real-time, maximizing the potential energy savings that are available in particular application. In Automatic On Mode, the lights turn ON when a person enters the room. In Manual-On Mode, the lights are turned ON by activating a momentary switch  (model # GMDS-*) that is connected to the sensor. When used with 2 level lighting (-R model only), Bi-level Automatic On can be achieved which allows Zone 1 to come on automatically upon occupancy. Zone 2 does not come on unless the occupant presses the optional momentary switch. When enabled, the daylighting feature (-R models only) prevents lights from  turning ON when the room is adequately illuminated by natural light. 

Cutsheets

Wall Mount Occupancy Sensor, Dual Tech, Low Voltage

Specifications

Technology:

  • Passive Infrared (PIR) and Ultrasonic (US)

Power Requirements:

  • Input:
    • 0-30 VDC from Greengate Switchpack or System
    • Maximum current needed is 25 mA per sensor
  • Output:
    • Open collector output to switch up to ten Greengate Switchpacks
    • Isolated Form C Relay in (-R models)
    • Isolated Form C Relay Ratings: 1A 30 VDC/VAC

Time Delays:

  • Self-Adjusting, 15 seconds/test, 5, 10, 15, 30 minutes

Light Level Sensing (-R Models):

  • 0 to 300 foot-candles

Operating Environment:

  • Temperature: 32°F - 104°F (0°C - 40°C)
  • Relative humidity: 20% to 90% Non-condensing
  • For indoor use only

Housing:

  • Durable, injection molded housing.  Polycarbonate resin complies with UL 94V-0
  • Size 4.4”H x 3.4”W x 2”D (112mm x 86.4mm x 50.8mm)

Mounting:

  • Mounts directly to ceiling tile, to a 4” square box and round mud ring or to 4” octagon box

LED Indicators:

  • Red LED for PIR detection; Green LED for Ultrasonic detection

Standards:

  • FCC Compliant
  • cULus Listed
  • RoHS Compliant
Features
  • MicroSet self-adjusting time delay and sensitivity
  • Optional built-in light level sensor
  • Optional BAS/HVAC isolated relay
  • NEMA WD7 Guide robotic method utilized to verify coverage patterns
  • Manual On feature for use with 1 or 2 momentary switches controlling 1 or more Switchpacks
  • Selectable Walk-Through Mode