LSCOS8I LightSync Digital Conditional Occupancy Sensor 8 Input Module LSCOS8I LightSync Digital Conditional Occupancy Sensor 8 Input Module

LightSync Occupancy Sensor Module

Model: LSOSM-P, LSOSM-R

The LightSync Digital Occupancy Sensor module is designed with 8 occupancy sensor inputs that provides power for multiple occupancy sensors. The LSOSM comes pre-configured as a standard occupancy sensor, and contain programmable conditionals for each Input. This allows you to utilize "AND"/"OR" logic schemes for any combination of inputs and pilots. Any input can be programmed to control any relay(s), group(s), or preset(s) in any or all panels. Each input has an associated LED on the board that activates when the input is closed.

Cutsheets

LightSync Occupancy Sensor Module

Wiring Diagrams

LightSync Conditional Occupancy Sensor 8 Input Module (WD0608)

Installation Guides

LightSync Conditional Occupancy Sensor 8 Input Module (ID0625)

Specifications

Safeguards: 

  • Optically isolated inputs protect electronics 

Physical: 

  • 2.75” Wide X 3.5” High 
  • Easy non-screw push-to-connect terminals 
  • Digital addressing switches 
  • RJ45 connectors for data line connection 
  • Remote (R) option provided in a 6.5"x9.25"x2.50" enclosure with 1/2" connector and screw cover. 

Electrical: 

  • Electronics powered from LightSync data line 
  • Input: 120/277VAC @ 400mA 
  • Output: 24VDC @ 800mA 
  • Current limited circuit 

Operating Environment: 

  • Location: Interior space 
  • Operating Temp.: 0° to 50° C  
  • Humidity: 10% - 90% Non-condensing  
  • Atmosphere: Non-explosive/corrosive  
  • Vibration: Stationary 

Certifications and Approvals: 

  • FCC Part 15 
  • UL 
  • CUL 
Resources

Product Details

LightSync Conditional Occupancy Sensor 8 Input Module (PD0624)

Features
  • Made in the USA 
  • Digital CAT-5 Ready 
  • 8 Conditional occupancy sensor inputs per module 
  • Provides Power and inputs for occupancy sensors 
  • Programmable conditional logic 
  • Accepts 2 wire maintained or momentary closures 
  • Connectors are non-screw push-to-connect type 
  • Switch closure LED status for each input 
  • Optically isolated inputs to protect electronics 
  • Panel mount (P) installs directly in the panel 
  • Remote mount (R) provided with electrical enclosure 
  • Power from 120/277VAC power supply 
  • Software logic programming provided